An Assessimus Group Company
All products made in the USA

Various

RFI/EMI Current Probes and Injection Probes

RFI/EMI Current Probes and Injection Probes

Description

CURRENT PROBES
Current probes required by various EMI specifications (such as MIL-STD-461/2) are toroidal transformers designed to measure RF currents on active power lines or other conductors.

APPLICATION
A current probe is used as a “pick-up” device for measuring RF current in single conductors or cable bundles when connected to the 50 Ω input
of a radio frequency interference measuring receiver or spectrum analyzer.

DESCRIPTION
Direct connection to the conductor carrying EMI current is not necessary, since the probe may be opened for insertion of the conductor into the window of the toroid and then closed again to form a toroidal transformer with the conductor acting as a one-turn primary.

A correction factor graph is provided to convert measured µV to EMI µAs. When the EMI current is measured in dB above 1 µV as indicated on a conventional EMI meter, the correction factor will convert the measurement to dB above 1
µA. The correction factor is the inverse of the transfer impedance, Zt. Each probe is shipped with a graph of the correction factor versus frequency, keyed
to the serial number on the probe.

INJECTION PROBES
Specifications require the injection of large high frequency currents into cable bundles and individual wires, using inserted secondary toroidal transformers placed around the conductors being tested.

APPLICATION
High power RF amplifiers with 50 Ω output impedance are used to deliver voltage to the injection probe. The wire or cable through the window of the probe acts as a secondary of the toroidal transformers. This test method is intended to be used instead of earlier methods, such as CS-01, CS-02, and RS-02 of MIL-STD-461.

DESCRIPTION
Bulk current injection probes are available in two styles:
1. Fixed window style where the wire(s) under test must be passed through the window.
2. A split toroidal design where the probe can be opened up and clamped over the wire(s) under test.

Each probe is calibrated for insertion loss and transfer impedance in a test fixture designed for the particular window size. This fixture provides a signal path with a low Voltage Standing Wave Ratio (VSWR). A typical fixture is Solar Type 9125-1, used for probes with 32 to 44 mm diameter windows. Ask for details on this and other test fixtures.

Injection probes currently available are described later in this section. Development of new styles is ongoing. If a probe meeting your requirements is not found on the list, send us details and we will provide a solution.

TECHNICAL INFORMATION
Current probes used as receptors are known as “inserted primary toroidal transformers” for connection
to EMI receivers. Injection probes which deliver high RF currents into wires through the window are
called “inserted secondary toroidal transformers”.

The maximum voltage carried on wires through the window is limited only by the insulation of the wires. Maximum primary current in the wires through the window of current probes is listed in the table in the Specifications tab (symbol lp).

The signal input to injection probes is rated in W from the signal source as indicated in the table in the Specifications tab.

Development is continuing on new and useful probes, both current measuring sensor probes and high wattage injection probes. The following is a partial list. As time goes on, the list will grow. If you do not see what you need, just ask.

Specifications

CLAMP-ON CURRENT PROBES

Maximum PRI. (pl) current, A

Type number

Window
diameter
Nominal
ZT Ω
DC to 60 Hz 400 Hz RF (CW) Pulse Frequency range

9124-1N

1.25″ (32.0 mm)

0

.001

200

70

50

5000

1 kHz – 200 MHz

9205-1

1.25″ (32.0 mm)

0

.33

800

800

50

100 20 Hz – 8 MHz

9118-1

1.25″ (32.0 mm)

0

.10

350

150

22

500 500 Hz – 200 MHz

9134-1

1.25″ (32.0 mm)

0

.70

500

400

5

100 20 Hz – 100 MHz

6741-1

1.25″ (32.0 mm)

0

.70

350

225

5

100 10 kHz – 100 MHz

9207-1

1.25″ (32.0 mm)

1

.0

800

450

4

.2

100 20 Hz – 150 MHz

9209-1

1.25″ (32.0 mm)

1

.0

800

800

100

200 20 Hz – 30 MHz

9145-1

1.25″ (32.0 mm)

5

350

350

42

100 10 kHz – 152 MHz

9123-1N

1.25″ (32.0 mm)

1-5

200

200

40

60 10 kHz – 500 MHz

9214-1

1.25″ (32.0 mm)

5

600

600

21

200 20 Hz – 150 MHz

9215-1N

1.25″ (32.0 mm)

1-5

400

350

40

100 20 Hz – 500 MHz

9231-1

1.25″ (32.0 mm)

.010

300

200

7

3000 1 kHz – 200 MHz

9219-1N

1.25″ (32.0 mm)

.025

400

300

150

200 20 Hz – 20 MHz

9250-1N

1.25″ (32.0 mm)

.10

200

200

10

200 10 kHz – 450 MHz

9257-1N

2.62″ (67.0 mm)

4

500

500

200

200 20 Hz – 30 MHz

9258-1N

2.62″ (67.0 mm)

5

500

500

100

200 20 Hz – 100 MHz

9261-1N

2.62″ (67.0 mm)

2

500

500

2

.6

100

20 Hz – 200 MHz

9263-1N

2.62″ (67.0 mm)

.03

500

500

80

200 20 Hz – 100 MHz

9301-1N

2.62″ (67.0 mm)

8

350

350

60

200 20 Hz – 500 MHz

9303-1N

2.62″ (67.0 mm)

.001

500

200

100

5000 20 Hz – 100 MHz

9305-1N

2.62″ (67.0 mm)

1

500

500

2

.3

200 20 Hz – 200 MHz

9306-1N

2.62″ (67.0 mm)

.005

800

300

14

5000 1 kHz – 100 MHz

9307-1N

2.62″ (67.0 mm)

.005

300

300

60

5000 20 Hz – 100 MHz
21406-1N 2.62″ (67.0 mm) .01

350

350

40

2200 100 Hz – 30 MHz

We provide equivalents for most Stoddart and Eaton probes.

CLAMP-ON INJECTION PROBES

Insertion loss

Type No.

Window
diameter
Winding
current
Rated W Under 6 dB Under 10 dB Under 15 dB Under 20 dB Frequency range

9108-1N

1.25″ (32 mm) 10 50 —

—

120 kHz – 70 MHz 60 kHz – 150 MHz 10 kHz – 200 MHz

9142-1N

1.50″ (38 mm) 50 200 10 MHz – 350 MHz 5 MHz – 430 MHz 2.5 MHz – 500 MHz 1.5 MHz – 500 MHz 2 MHz – 500 MHz

9144-1N

1.50″ (38 mm) 26 100 — 200 kHz – 8 MHz 70 kHz – 90 MHz 40 kHz – 100 MHz 4 kHz – 100 MHz

9217-1N

1.50″ (38 mm) 26 100 — 200 kHz – 5 MHz 80 kHz – 100 MHz 50 kHz – 100 MHz 10 kHz – 100 MHz

9335-2

1.50″ (38 mm) 10 kHz – 100 MHz

9607-1N

1.25″ (32 mm) 10 50 — 500 kHz – 1 MHz 200 kHz – 30 MHz 120 kHz – 300 MHz 10 kHz – 300 MHz

9719-1N

1.50″ (38 mm) 60 200 5 MHz – 100 MHz 3 MHz – 200 MHz 1.5 MHz – 200 MHz 700 kHz – 200 MHz 10 kHz – 200 MHz

2216-1N

1.50″ (38 mm) 26 100 — — 50 kHz – 30 MHz 10 kHz – 100 MHz 1 kHz – 100 MHz

Injection probes can also be used as current probes. A correction factor graph and instructions for its use are supplied.

CALIBRATION FIXTURES

Type No.

Description

9125-1

For injection probes, 1.5″ (32 mm – 44 mm) diameter window. 20 Hz to 500 MHz. Type N connectors.

9125-2

For Solar 9119-1N Probe and similar, 1.25″ (32 mm) diameter window. 400 MHz to 3 GHz. Type N connectors.

9251-1

For Eaton, Stoddart and Solar probes, 1.25″ (32 mm) diameter window. 20 Hz to 500 MHz. Type BNC connectors.

9254-1

For Eaton, Stoddart and Solar probes, 2.62 ” (66 mm) diameter window. 20 Hz to 500 MHz. Type N connectors.

9321-1

For Eaton, Stoddart and Solar probes, 0.75″ (19 mm) diameter window, totally enclosed. 20 Hz to 1.5 GHz. Type BNC connectors.

9330-1

For Eaton, Stoddart and Solar probes, 1.25″ (32 mm) diameter window, totally enclosed. 20 Hz ≈ 1. GHz. Type N connectors.

2925-1

Fixtures for Solar Type 9335-2 Probe. 20 Hz to 100 MHz. Type N connectors. (9357-1 has been discontinued

NOTE: Except for Type 9125-1 and 2925-1, the probes are supported and centered in the fixture.

Need a custom configuration?

Send your specifications and our engineers will quote a solution.